Description
Description
It has an alarm memory function where the LED still lights after the alarm state is over.
It is battery powered by alkaline batteries.
It is addressable and occupies one position in the alarm.
Technical data
Technical data
Power | 3x LR6 (AA) type alkaline batteries, 1.5 V Warning: batteries are not included |
---|---|
Typical battery lifetime | approx. 3 years |
Communication band | 868.1 MHz, Jablotron protocol |
Effective Radiated Power (ERP) | 10 mW |
Communication range | approx. 300 m (unrestricted area) |
Dimensions | diameter 126 mm, height 50 mm |
Weight | 150 g |
Smoke detection | optical light scattering |
Smoke detector sensitivity | m = 0.11 - 0.13 dB/m pursuant to EN 54-7 |
Heat detection | class A2 according to EN 54-5 |
Alarm temperature | +60 °C to +70 °C |
Operating temperature range | -10 °C to +80 °C |
Complies with | EN 54-5, EN 54-7, EN 54-25 |
Also complies with | ETSI EN 300220, EN 50130-4, EN 55022, EN 60950-1 |
Can be operated according to | ERC REC 70-03 |
Recommended screw | 2x ø 3.5 x 40 mm (countersunk head) |