Description
Description
This built-in module can be directly integrated into the detector.
- One input of the module has a fixed Tamper signal, the second input reports an alarm signal and the third input is used to report a fault of a connected device or to report a special “Masking” signal (for detectors with an Anti-masking function).
- The module can also be used for the connection of a CT-01 roller blind detector.
- The module can be used to control programmable PG outputs.
- It supports setting of a minimum activation time for alarm triggering (0.1 s - 300 s).
- The detector features status as well as impulse activation.
- The module is a device of the JABLOTRON 100+ system, is addressable and occupies one position in the system.
Technical data
Technical data
Power | from control panel BUS 12 V DC (9…15 V) |
---|---|
Current consumption - Nominal consumption - to calculate backup | 8 mA all inputs connected to GND (+ consumption of connected devices) |
Current consumption - Maximal consumption - for cable selection | 12 mA (+ consumption of connected devices) |
Maximum allowed current of the connected detector | 50 mA |
Dimensions | 16 x 30 x 12 mm |
Weight | 8 g |
Classification | Security grade 2/environmental class II Note: valid only, if it is built-in to security grade 2 or higher certified housing |
- according to | EN 50131-1, EN 50131-3 (ACE type B) |
- environmental | Indoor general |
- operating temperature range | -10 to +40 °C |
- average humidity | 75 % RH non condensing |
- certification body | Trezor Test s.r.o. (no. 3025) |
Valid for installation of the module into a product certified for | security grade 2/environmental class II and also if the connection to the module is compatible. |
Also complies with | EN 50130-4, EN 55022 |
Documents to download (1)